Search FAQs
What are the Ground Fault Alarm pickup, dropout and time delay settings for Micrologic P and H trip units?
Issue: Ground Fault alarm settings for Micrologic 5.0P, 6.0P, 5.0H, 6.0H trip units
Product Line: Circuit Breakers
Environment: Masterpact NW and NT, Powerpact P and R, Compact NS
Resolution:
100-400 amp sensors have a pickup and dropout range of .3xIn - 1xIn with a 1-10 second time delay
600-1200 amp sensors have a pickup and dropout range of .2xIn - 1xIn with a 1-10 second time delay
1250-6300 amp sensors have a pickup and dropout range of .1xIn - 1200 amps with a 1-10 second time delay
1 amp increments
0.1 second increments
Product Line: Circuit Breakers
Environment: Masterpact NW and NT, Powerpact P and R, Compact NS
Resolution:
100-400 amp sensors have a pickup and dropout range of .3xIn - 1xIn with a 1-10 second time delay
600-1200 amp sensors have a pickup and dropout range of .2xIn - 1xIn with a 1-10 second time delay
1250-6300 amp sensors have a pickup and dropout range of .1xIn - 1200 amps with a 1-10 second time delay
1 amp increments
0.1 second increments
Released for:Schneider Electric USA
Explore more
Range:
Explore more
Range: