Issue:
How to connect to the OMT Web page of Tesys Island TPRBCEIP ?
Product Line:
Motor Management system Tesys Island
Environment:
IEC Contactors and Starters
Resolution:
There are two different methods,
OMT IPv6 Connection
1. Verify that the PC is connected to the same network as the bus coupler through a wireless or wired connection.
2. Access the Network window on the PC via the Navigation Pane in File Explorer (called Windows Explorer prior to Windows 8).
3. Under Other Devices, the TeSys island appears as "TeSysisland_xxxx." If the island does not appear, you may have to disable the firewall running on your PC.
4. Right-click "TeSysisland_xxxx" and select Properties. Result: The island properties are displayed.
5. Click the device web page link. This is the IPv6 IP address of the bus coupler. Result: The OMT launches in your default browser.
6. If you are taken to the page, "Your connection is not private", then perform the following steps: a. Click the Advanced button. b. Click the link Proceed to [xxxx::xxx:xxxx:xxxx:xx] (unsafe) to continue. Result: The OMT login screen is displayed on the screen.
7. Log in with the default username and password (admin, schneider18) and click Login. Result: The Change Password window opens.
8. Set a secure password and record it before continuing. Result: You are now logged in to the OMT and connected to the island.
OMT IPv4 Connection
1. Verify that your PC is connected to the same network as the bus coupler through a wireless or wired connection.
2. Configure your PC with the IPv4 IP address of 10.10.0.2 and the subnet mask of 255.0.0.0
3. Enter the address (https://10.10.0.1) of the bus coupler into the web browser on your tablet to access the OMT running on the bus coupler. NOTE: The recommended browsers are Chrome or Safari.
4. If you are taken to the page, "Your connection is not private": a. Click Advanced. b. Click the link "Proceed to 10.10.0.1 (unsafe)" to continue.
5. Log in with the default username and password (admin, schneider18) and click Login. The Change Password window opens.
6. Set a secure password and record it before continuing. NOTE: If you forget your password, a factory reset will be required to regain access to the OMT. You are now logged in to the OMT and connected to the island.
How to connect to the OMT Web page of Tesys Island TPRBCEIP ?
Product Line:
Motor Management system Tesys Island
Environment:
IEC Contactors and Starters
Resolution:
There are two different methods,
OMT IPv6 Connection
1. Verify that the PC is connected to the same network as the bus coupler through a wireless or wired connection.
2. Access the Network window on the PC via the Navigation Pane in File Explorer (called Windows Explorer prior to Windows 8).
3. Under Other Devices, the TeSys island appears as "TeSysisland_xxxx." If the island does not appear, you may have to disable the firewall running on your PC.
4. Right-click "TeSysisland_xxxx" and select Properties. Result: The island properties are displayed.
5. Click the device web page link. This is the IPv6 IP address of the bus coupler. Result: The OMT launches in your default browser.
6. If you are taken to the page, "Your connection is not private", then perform the following steps: a. Click the Advanced button. b. Click the link Proceed to [xxxx::xxx:xxxx:xxxx:xx] (unsafe) to continue. Result: The OMT login screen is displayed on the screen.
7. Log in with the default username and password (admin, schneider18) and click Login. Result: The Change Password window opens.
8. Set a secure password and record it before continuing. Result: You are now logged in to the OMT and connected to the island.
OMT IPv4 Connection
1. Verify that your PC is connected to the same network as the bus coupler through a wireless or wired connection.
2. Configure your PC with the IPv4 IP address of 10.10.0.2 and the subnet mask of 255.0.0.0
3. Enter the address (https://10.10.0.1) of the bus coupler into the web browser on your tablet to access the OMT running on the bus coupler. NOTE: The recommended browsers are Chrome or Safari.
4. If you are taken to the page, "Your connection is not private": a. Click Advanced. b. Click the link "Proceed to 10.10.0.1 (unsafe)" to continue.
5. Log in with the default username and password (admin, schneider18) and click Login. The Change Password window opens.
6. Set a secure password and record it before continuing. NOTE: If you forget your password, a factory reset will be required to regain access to the OMT. You are now logged in to the OMT and connected to the island.