Issue:
How to return Tesys Island to factory settings?
Product Line:
Motor Management system Tesys Island
Environment:
IEC Contactors and Starters
Resolution:
The TeSys™ island system can be reset to factory settings, returning the bus coupler to its out-of-the-box conditions. This is useful, for example, to quickly get to Test mode when building or modifying an island.
TeSys island accepts a Factory Reset command from the digital tool (TeSys island DTM or OMT) with exclusive control when the system is in Pre-Operational mode, Test mode, or Minor Event state. Upon receiving a Factory Reset command, TeSys island
1. Deletes the following files:
• system context files (active, pending, and SDP if present)
• SEDP files (including active, pending, or update)
• Users file
2. Automatically restarts
NOTE: When the Users file is deleted, any added users are removed. In addition, the group management and the administrative password are reset to default values. A Factory Reset command does not delete log files.
To perform a factory reset using the TeSys island DTM, follow the steps below:
1. In the TeSys island DTM, select Device > Factory Reset.
2. Click OK to perform the factory reset. • The island starts the reset procedure. • The PWR LED on the bus coupler is yellow. • The LEDs on the rest of the modules flash green.
Using the TeSys island OMT
To perform a factory reset using the OMT, follow the steps below:
1. Click the Admin Options panel.
2. Expand the System Settings section.
3. Click the Restore Factory Defaults button.
4. Click OK to continue with the factory reset. • The island starts the reset procedure. • The PWR LED on the bus coupler is yellow. • The LEDs on the rest of the modules flash green.
How to return Tesys Island to factory settings?
Product Line:
Motor Management system Tesys Island
Environment:
IEC Contactors and Starters
Resolution:
The TeSys™ island system can be reset to factory settings, returning the bus coupler to its out-of-the-box conditions. This is useful, for example, to quickly get to Test mode when building or modifying an island.
TeSys island accepts a Factory Reset command from the digital tool (TeSys island DTM or OMT) with exclusive control when the system is in Pre-Operational mode, Test mode, or Minor Event state. Upon receiving a Factory Reset command, TeSys island
1. Deletes the following files:
• system context files (active, pending, and SDP if present)
• SEDP files (including active, pending, or update)
• Users file
2. Automatically restarts
NOTE: When the Users file is deleted, any added users are removed. In addition, the group management and the administrative password are reset to default values. A Factory Reset command does not delete log files.
To perform a factory reset using the TeSys island DTM, follow the steps below:
1. In the TeSys island DTM, select Device > Factory Reset.
2. Click OK to perform the factory reset. • The island starts the reset procedure. • The PWR LED on the bus coupler is yellow. • The LEDs on the rest of the modules flash green.
Using the TeSys island OMT
To perform a factory reset using the OMT, follow the steps below:
1. Click the Admin Options panel.
2. Expand the System Settings section.
3. Click the Restore Factory Defaults button.
4. Click OK to continue with the factory reset. • The island starts the reset procedure. • The PWR LED on the bus coupler is yellow. • The LEDs on the rest of the modules flash green.