{}

Our Brands

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
In Ecostruxure power commission, What user should do when the see " Application failed to launch " PORT In USE error while launching
1. Go to launch logs by accessing this path in your local computer
C:\Users\SESXXXX\AppData\Roaming\Schneider-Electric\Ecoreach\Logs
User directory
2. Open EPC EPCLaunchLog.txt logs
3.Scroll down to view logs with latest date
4. when user sees logs with text  as shown below : For example
launch- port in use

5. Node server is not up- which refers , NODE Socket Server port  (8084)is occupied by some other application .
6. To free up the occupied ports , Please refer attached troubleshooting guide (Page -30 to 32) with the help of local IT team.
7. Refer prerequisite for successful installation and launch with the help of local IT team https://download.schneider-electric.com/files?p_Doc_Ref=DOCA0134EN&p_enDocType=User+guide&p_File_Name=EcoStruxure+Power+Commission+Installation+Guide.pdf

8. Launch Ecostruxure power commission.

Schneider Electric USA

Attachment(s)
Trouble shooting steps for EPC Launch issue.pdf [2.61 MB]
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.