Tesys Island, this avatar As configured cannot be added due to capacity constraings of the island
Issue:
I cannot add an avatar to the configuration of my Island in Somove

This message shows up:

Many avatars

Max size 3 starters


Product line:
IEC Contactors and Starters

Environment:
Tesys Island Motor management solution

Solution:
As the messages state, there is something about your configuration which means it is too large/invalid.  As a reminder, the constraints are:
  • Maximum of 21 bus devices, (20 starters + 1 VIM or 20 starters + 1 SIM).  21 starters is invalid
  • Maximum of 5 Frame 3 devices active (a reverser avatar counts as 1 frame 3, because only one is ever on at a given moment)
Maximum of ~15 avatars (depends on specific avatars) with Profibus

Suggest to remove an avatar, remove an IO module, or split up into two islands if this constraint arrives

Schneider Electric USA

Tesys Island, this avatar As configured cannot be added due to capacity constraings of the island
Issue:
I cannot add an avatar to the configuration of my Island in Somove

This message shows up:

Many avatars

Max size 3 starters


Product line:
IEC Contactors and Starters

Environment:
Tesys Island Motor management solution

Solution:
As the messages state, there is something about your configuration which means it is too large/invalid.  As a reminder, the constraints are:
  • Maximum of 21 bus devices, (20 starters + 1 VIM or 20 starters + 1 SIM).  21 starters is invalid
  • Maximum of 5 Frame 3 devices active (a reverser avatar counts as 1 frame 3, because only one is ever on at a given moment)
Maximum of ~15 avatars (depends on specific avatars) with Profibus

Suggest to remove an avatar, remove an IO module, or split up into two islands if this constraint arrives

 

Schneider Electric USA

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.