{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
Tesys Island : Parameter apply is not allowed in current state of the device (Machine Expert)
Issue:
Changing a parameter or storing a new configuration from machine expert to Tesys Island is not possible due to following message:

Not exclusive control over the island


Product line:
IEC Contactors and Starters

Environment:
Tesys Island Motor management System

Resolution:
Changing settings or storing a new configuration is only allowed by one tool at a time.  Tool includes OMT and DTM.  Check to see if you have the OMT or another DTM connected and close that connection, then retry.

Schneider Electric USA

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: