Are the lugs and power distribution connector (PDC) on PowerPacT circuit breaker lugs approved for use with a sleeve / ferrule / thin copper shim stock?

Product Line:

PowerPacT H, J, L M, P, R Circuit Breakers

Resolution:

No, mechanical lugs and power distribution connectors (PDC) are not approved for use with a sleeve / ferrule / thin copper shim stock. This applies to PowerpacT B, H, J, L, M, P and R frame breakers.

A sleeve / ferrule / thin copper shim can break when being compressed and strands of wire can get caught up in the wire binding screw causing a false torque reading resulting in a loose connection.

Schneider Electric USA

Are the lugs and power distribution connector (PDC) on PowerPacT circuit breaker lugs approved for use with a sleeve / ferrule / thin copper shim stock?

Product Line:

PowerPacT H, J, L M, P, R Circuit Breakers

 

Resolution:

No, mechanical lugs and power distribution connectors (PDC) are not approved for use with a sleeve / ferrule / thin copper shim stock. This applies to PowerpacT B, H, J, L, M, P and R frame breakers.

A sleeve / ferrule / thin copper shim can break when being compressed and strands of wire can get caught up in the wire binding screw causing a false torque reading resulting in a loose connection.

Schneider Electric USA

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.