{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
EDCO PC642C / ASCO 175 - How to test to see if Good / Bad
PCB1BWKEY Diagram.JPG


1.  Measure and record the resistance across the following pins on the PCB1BWKEY Plug-in Base (with the EDCO PC642C / ASCO 175 module plugged into the base and all wires disconnected):
> 2-3, 4-5, 6-7, 8-9
2.  If resistance is less than 8 ohms on the EDCO PC642C / ASCO 175 module is good
If resistance is greater than 8 ohms the  EDCO PC642C / ASCO 175 module is bad and should be replaced.

For additional question please reach out to the Schneider Electric SPD Advanced Technical Support Team at 1-800-577-7353.

Schneider Electric USA

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: