{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
Is It possible to update BMENUA0100 firmware via M580 CPU ?
Yes, It is possible to update the BMENUA0100 module firmware via the SERVICE port of the M580 CPU:

1- The module should be on "Secured" mode ( more details here: https://www.se.com/id/en/faqs/FAQ000235297/)

2- A user account with "Installer" role must be created via the module webpage ;

User Management


3-  With EcoStruxure Automation Device Maintenance tool, configure the BMENUA0100 backplane IP address to connect to the module:

IP configuration

4- Use the user account with the "installer" role previously created:

Credentials


5- If it was the first time you connect to the module, It could ask to trust its certificate:

Certificate information

6- Select the firmware to upload:

Firmware selection


7- Launch the update and follow the steps:

Update process
Best Regards.





Schneider Electric USA

Explore more
Product:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Product: