What is 9080LBA364101 minimum enclosure size?

Issue:
Min Enclosure Size

Product Line:
Nema Type LB power distribution blocks.

Environment:
NEMA Power distribution Blocks

Cause:
To clarify minimum enclosure size for 9080LBA364101

Resolution:

Investigated Minimum Enclosure size for this 9080LBA364101 is 16in x 12in x 16in. also applicable for 9080LBA164101