{}

Our Brands

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
Using the BMENOR2200 with DNP3 Group 12 Variation 1 binary output TCC command.
In order to use the BMENOR2200 Ethernet module with Group 12 Variation 1 binary output Trip Close Command, the DNP3 point must be configured as shown:
 
  • Configure the Trip Close mode.image.png
  • Configure the binary output point TCC for Trip_Close.a1



The format for the DNP3 Group 12 Variation 1 'Trip Close Command' select range specifier and object prefix sent by the device must be according to the following example:

a2




a3



a4


a5
 
 

Schneider Electric USA

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.