Where to find wiring instructions for RMCV60BD
Issue:
RMCV60BD instruction sheet does not show the wiring instructions.

Product line:
Interface and Control Relays

Environment:
Harmony Analog SE relays

Resolution:

See the attached wiring schematic and description:

Wiring terminals RMCV

> A1(+) & A2(-) are the control voltage terminals for 24 V DC (+/- 20 %).

> The switch at the top is selected based on the input voltage type, that is AC or DC.

> The input voltage coming from your battery is wired to only one of the V# terminals depending on the voltage range. Wire (+) to terminal:

  • V1 if input voltage is between 0...50 V
  • V2 if input voltage is between 0...300 V
  • V3 if input voltage is between 0...500 V

and (-) to terminal IPG.

> The switch a the bottom is selected based on the output type

> The output terminals are Vo (+) and OPG (-)