Can I make a line-side tap connection from the Schneider Inverter to the Schneider Pulse CSED Panel?
No, you cannot make a line-side tap connection from the Schneider Inverter to the Schneider Pulse CSED Panel. Line-side tap connection requires that the wires from the inverter are connected to the service wires on the line side of the service disconnect. The inverter output circuit should be terminated on a circuit breaker installed on the bus bar inside the Pulse CSED.

Schneider Electric USA

Can I make a line-side tap connection from the Schneider Inverter to the Schneider Pulse CSED Panel?
No, you cannot make a line-side tap connection from the Schneider Inverter to the Schneider Pulse CSED Panel. Line-side tap connection requires that the wires from the inverter are connected to the service wires on the line side of the service disconnect. The inverter output circuit should be terminated on a circuit breaker installed on the bus bar inside the Pulse CSED.

Schneider Electric USA

Explore more
Product:
Explore more
Product:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
Explore more
Product:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.