{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
IMDMFLK1 - Charge indicator not showing Full Percentage

Detailed procedure with photos are in the attachment . Kindly refer it before any action .
This procedure  to be carried out only by Schneider authorized personals.
•Have a screwdriver handy to remove the front panel of the Kit.
•Have a Multimeter handy to measure the Battery voltage.
•Connect the current connector to the current probe to ensure the buzzer alarm is off.
•In this document the Battery Indicator Calibration button will be abbreviated as BICB.
Procedure for charge  Indicator configuration

Schneider Electric USA

Attachment(s)
IMDMFLK1 – Battery Indicator Calibration_reviewed.pdf [732.76 KB]
Explore more
Product:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Product: