You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
Issue:
Altivar 71 or 61 analog output range for motor current.
Product Line:
ATV61 and ATV71
Environment:
All
Cause:
Analog output to show motor current is 2 times the drives rated nameplate motor current.
Resolution:
The range is 0 to 200% of the drive nameplate current.
You can scale this output by going into the Input and outputs section menu 1.5
Find the AO1 that is assigned to motor current and set he max scale to 50% this will give you the output of 1X the drives motor current on the analog output.
CTA-ID : 2029689
Altivar 71 or 61 analog output range for motor current.
Product Line:
ATV61 and ATV71
Environment:
All
Cause:
Analog output to show motor current is 2 times the drives rated nameplate motor current.
Resolution:
The range is 0 to 200% of the drive nameplate current.
You can scale this output by going into the Input and outputs section menu 1.5
Find the AO1 that is assigned to motor current and set he max scale to 50% this will give you the output of 1X the drives motor current on the analog output.
CTA-ID : 2029689