{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.

What is the accuracy of the Premium PLC CPU real time clock.

Article available in these languages: Japanese

Real time clock accuracy:

Accuracy of the real time clock is one second (%SW50) +/- 200ms.

Resolution of the real time clock is one second (%SW50) +/- 200ms,because 200ms is the refresh rate of the RTC.
Accuracy error:
The accuracy error of the quartz oscillator is:
1. At 0 and 70°C : -101/20 ppm, error in second/day is -8.7/1.7, in minute/year is -53/11.
2. At 25°C: -20/20 ppm, error in second/day is -1.7/1.7, in minute/year is -11/11.

Schneider Electric Vietnam

Explore more
Range:
Modicon Premium
Explore more
Range:
Modicon Premium
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.