{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.

What is the difference between QMB and QMJ fusible branch units?

Issue:
Product Design Features

Product Line:
QMB QMJ panelboards and switchboards

Resolution:
The QMJ switches are suitable for use with Class J fuses only.

The QMB switches as standard accept a Class H or K fuses for use on systems up to 10 kAIC and Class R fuses with a Class R fuse kit for use on systems up to 200 kAIC. Then many of the QMB switches can be modified to accommodate Class J fuses by moving the load base assembly to a location marked on the enclosure. Also, some of the QMJ switches will be in a smaller footprint enclosure.

Schneider Electric Vietnam

Explore more
Range:
QMB Fusible Power Distribution Panelboards
Explore more
Range:
QMB Fusible Power Distribution Panelboards
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.