Issue:
HCM interior cannot take KC circuit breakers
Product Line:
Panelboard, Circuit Breakers
Environment:
ILine Panelboard and Circuit Breakers
Resolution:
Size wise the KC will fit. However, the KC breaker needs a vented trim to allow the gases to escape on a high level fault. The HCM trim is not vented. But the Powerpact JJ and JL do not need the vented trim so they can be used.