{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.

Can the ATV312 be programmed for a fallback speed in the event of a loss of the 4-20mA speed reference signal?

Issue:
ATV312 for a fallback speed configuration in the event of a loss of the 4-20mA speed reference signal

Product Line:
ATV31 and ATV312 drives

Environment:
All

Cause:
NA

Resolution:
Yes.  In the FLt menu, program LFL to LFF and then set LFF to the desired fall back speed in Hz.

Important note:
The fallback speed will take precedence, regardless of whether you are currently using the 4-20mA signal for speed control.

For example, if you are currently controlling speed with a potentiometer on AI1, and your 4-20mA signal drops on AI3, the drive will use the fallback speed even though you're currently not using the 4-20mA signal. Therefore, if you are not currently using the 4-20mA signal for speed control, you may want to set LFL to 'no', which will ignore 4-20mA signal loss.

Details on these parameters are found in the ATV312 Programming Manual on page 96.

manual screen shot
CTA-ID : 2061337

Schneider Electric Vietnam

Attachment(s)

ATV312_programming_manual_EN_BBV46385_04.pdfATV312_programming_manual_EN_BBV46385_04.pdf [1.84 MB]
ATV312 LFL and LFF parameters.JPG.jpgATV312 LFL and LFF parameters.JPG.jpg [120.32 KB]
Explore more
Range:
Altivar 312Altivar Plus Engineered Drives
Explore more
Range:
Altivar 312Altivar Plus Engineered Drives
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.