{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.

Video: How are preset speeds configured on Altivar 212 Drives?

Issue:
Preset speeds configured on Altivar 212 Drives.

Product Line:
Altivar 212 ATV212

Environment:
All ATV212 models

Cause:
Drive is to run at 2 different specific speeds.

Resolution:
The slower speed is assigned to LL and a logic input activates the higher speed which is assigned to Sr1.
For example, logic input R is assigned F112 = 6.  When R is low, the drive runs at speed LL.  When R is high, the drive runs at speed Sr1.

Note that the Preset Speed control feature is only active when the drive is in logic input control, CMOd=0, and in Remote mode.

Schneider Electric Vietnam

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.