{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.

Video: How to set 4-20mA with terminal control as start/stop on ATV312 drive?

Issue:
Wiring and configuring 2-wire terminal start/stop run control on Logic Input 1 (LI1 + 24vdc) and 4-20mA speed control via Analog Input 3 (AI3) on Altivar 312.

Product Line:
ATV312

Environment:
All models in range.

Cause:
Drive set up and wiring.

Resolution:
Go to menu CtL (Control) - Change parameter FR1 to AI3.  The speed reference default is AI1.  The start/stop command default in 2 wire control between +24 and LI1.

Schneider Electric Vietnam

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: