{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.

How to set up the basic PID control on the ATV61 or ATV71 drives?

Issue:
PID setup for the ATV61 or ATV71 drives.

Product line:
ATV61 and ATV71

Environment:
All models, all serial numbers

Cause:
PID set up to maintain pressure control with a fixed pressure set point

Resolution:
1.7 Application function menu -> PID regulator

PID feedback assign(PIF)= signal for the PID loop feedback
Min PID feedback(PIF1)= 0 (example only)
Min range of PID signal
Max PID feedback(PIF2)= 1000 (example only)
Max range of PID signal
Min PID reference(PIP1)= 100 (example only)
Min range of PID window
Max PID reference(PIP2)= 900 (example only)
Max range of PID window
Act. internal PID ref(PII)= Yes set point is from internal PID ref(rPI)
Internal PID set point
PID Prop. gain(rPG)= 0.75 (example only)
PID Loop response
PID integral gain(rIG)= 0.1 (example only)
PID Loop response
PID ramp(PrP)= 6 seconds (example only)
Auto/Manual Assign(PAU)
Switch to and from PID mode
Acceleration 2(AC2)= 5 seconds factory default
Acceleration before the VFD enters the PID window
Manual reference(PIn)
Speed reference when Auto/Manual assign(PAU) input is active

ATV61_Programming manual

Schneider Electric Vietnam

Explore more
Range:
Altivar 71Altivar 61
Explore more
Range:
Altivar 71Altivar 61
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.