{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.

ATV61: Is there a way to monitor or read the DC bus on the drive HMI?

Issue:
Looking to monitor or read the DC bus on the ATV61 drive HMI.

Product Line:
Altivar 61/71  ATV61 ATV71

Environment:
All

Cause:
Limited access to terminals

Resolution:
There are no monitoring options for reading the DC Bus from the drive HMI.
In the monitor menu it will display "Mains Voltage".
To calculate the DC Bus voltage:
If you multiply this value by 1.414 (sq root of 2) the result will be the value of the DC bus.
However, the drive does a calculation with the DC bus voltage to determine the mains voltage (line supply).

Schneider Electric Vietnam

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: