{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.

How to troubleshoot a TSX Momentum Interbus communication problem using Concept programming software.

When using Interbus, if the Interbus tophats do not show a solid green BA and RC light, you have a network problem. To view the status of the Interbus network, you will want to go to the Controller Status and look at word 4. The value in word 4 points to the last module it can communicate with (ie.. a value of 6 is pointing at the 6th module). The possibilities are one of the following:
1) the output driver on module 6 is bad
2) the cable is bad from module 6 to module 7
3) the 7th module or top hat is bad.

Schneider Electric Vietnam

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: