Issue
Minimum pulse or duration required on a IOX or IOC module on a CM4000 series meter
Product Line
CM4000 series meter
Environment
Hardware Specifications
Resolution
The minimal pulse duration per input on the CM4000 IOX or IOC is 15ms when the control power to the meter is DC voltage. For AC voltage to the control power the minimal input pulse duration is 23ms.
Minimum pulse or duration required on a IOX or IOC module on a CM4000 series meter