{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.

Why the vfd will not ramp to the correct speed of the 0-10V signal on AI1?


Issue:
The analog input signal do not match what is being sent.

Product line:
Altivar 61/71

Environment:
All models, all serial numbers

Cause:
The AI1 input is a bipolar input.  If AI1 negative is not referenced to common the drive is looking for a range of 20 V dc ( +10 to  - 10).

Resolution:
Verify the factory installed jumper between AI1- and common terminals is installed.

Schneider Electric Vietnam

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.