{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.

How do you reset the fault over modbus on the ATS22 soft starter?

Issue:
Needs to reset the fault over modbus on the ATS22 soft starter.

Product Line:
Altistart ATS22

Environment:
All

Cause:
Fault reset over modbus

Resolution:
The CMD register is word 752.  If  you set bit 3 to a 1 on the CMD word  it will reset any resetable faults.

Schneider Electric Vietnam

Attachment(s)

Modbus address words for the ATS22.pdfModbus address words for the ATS22.pdf [332.67 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: