Can I connect my VW3A1101 keypad directly to my PC to download / upload drive configuration files?

Article available in these languages: Spanish

Issue:
Download/upload drive configuration files by connecting my VW3A1101 keypad directly to my PC.

Product Line:
VW3A1101 graphic HMI.

Environment:
All firmware revisions, all serial numbers

Cause:
Customer transferred files from several drives onto one keypad and now needs to copy them to their PC.

Resolution:
No, it is not possible to transfer files from the VW3A1101 keypad directly to a PC.  The keypad is used to store a backup copy of the program for transfer back into the same drive.  In order to copy the program from the drive in a format that can be easily transferred to a PC, either connect your PC directly to the drives Modbus RTU port via the RS232 to RS485 converter cable (TCSMCNAM3M002P) and use SoMove software to download the parameter, or use a multiloader hand held device.

Schneider Electric Vietnam

Explore more
Range:
Model 6 Motor Control Centers with AC Drives
Category:
AC Drives and Soft Starters
Explore more
Range:
Model 6 Motor Control Centers with AC Drives
Category:
AC Drives and Soft Starters
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.