{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.

Can M241/M218/M238/M221 PTO only use one output, and another PTO output be used as normal output?

No, for M241/M218/M238/M221, one PTO channel must use two outputs! Any PTO output can not be used as normal output when PTO is configured!

Schneider Electric Vietnam

Explore more
Range:
Modicon M241Modicon M221
Explore more
Range:
Modicon M241Modicon M221
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.