You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
Issue:
ATV61 and ATV71 using high leg, corner grounded or ungrounded delta system.
Product Line:
Altivar ATV61 ATV71
Environment:
All
Cause:
Needs to know if there is anything that needs to be done on the drive when using a high resistance to ground system?
Resolution:
You can use the drive on an high resistance to ground system however you will need to deactivate the ground connection on the RFI filter board. See the examples below for the low horsepower drive and the high horsepower drives.
See Attachment
ATV61 and ATV71 using high leg, corner grounded or ungrounded delta system.
Product Line:
Altivar ATV61 ATV71
Environment:
All
Cause:
Needs to know if there is anything that needs to be done on the drive when using a high resistance to ground system?
Resolution:
You can use the drive on an high resistance to ground system however you will need to deactivate the ground connection on the RFI filter board. See the examples below for the low horsepower drive and the high horsepower drives.
See Attachment