{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.

What can cause an Err5 fault on the S-Flex ATV212 drives?

Issue:
ATV212 Drive is getting Err5 fault on display?

Product Line:
Altivar ATV212, S-Flex

Environment:
All

Cause:
Started to get the Err5 fault after setting F829 to Lowworks control

Resolution:
Err5 is a serial communications error.  If you program F829 to be controlled over the network, make sure you are sending a signal within the programmed timeout period.
Check timeout setting on F803.
Check the remote HMI cable if they used.
Check the F829 settings, try setting F829 back to 1 and cycle power to see if it will clear the Err5.
If the Err5 fault is cleared, set F829 back to 5 for Lonworks communication.

Schneider Electric Vietnam

Explore more
Range:
Altivar 212S-Flex Altivar 212
Explore more
Range:
Altivar 212S-Flex Altivar 212
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.