{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.

How can you read the status of local or remote via binary point thru bacnet?

Issue:
Reading the status of local or remote via binary point (BacNet)

Product Line:
Altivar 212

Environment:
All serial numbers for Altivar 212

Cause:
N/A

Resolution:
Under the Binary Value Objects Instance, #4 reads and indicates if the drive is locally controlled or not. It is dependent on several other factors as well.
Please reference the chart below

Binary Value


Schneider Electric Vietnam

Explore more
Range:
Altivar 212
Explore more
Range:
Altivar 212
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.