Issue:
Smallest size motor that can used on the ATS22 soft starters
Product Line:
Altistart ATS22
Environment:
All
Cause:
N/A
Resolution:
The rated motor current can be programmed to 40% of the Soft starters current ratings.
Example if the Soft starter rated current (IcL) is 17 amps you can decrease the motor nominal current (In) parameter of the soft starter to as low as 40% or 17*.4 = 6.8 amps.