You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
Issue:
ATV212 not following customized ramp-up and ramp-down parameters.
Product Line:
Altivar 212
Environment:
All
Cause:
Not following ramping setup
Resolution:
Press mode to go to AUF.
Arrow down to ACC and enter. This is the ramp up time the drive will follow upon run command.
Go into AU1 and enter. Set it to 0 to deactivate auto ramp and follow your ramp up time.
Set AU1 to 1 to allow the drive to follows its own auto ramp up time.
ATV212 not following customized ramp-up and ramp-down parameters.
Product Line:
Altivar 212
Environment:
All
Cause:
Not following ramping setup
Resolution:
Press mode to go to AUF.
Arrow down to ACC and enter. This is the ramp up time the drive will follow upon run command.
Go into AU1 and enter. Set it to 0 to deactivate auto ramp and follow your ramp up time.
Set AU1 to 1 to allow the drive to follows its own auto ramp up time.