{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
How do I access the Com Scanner Input and Output tables on the Altivar Process Drive?

Article available in these languages: Finnish

Issue:
Access the Comm Scanner Input and Output tables on the Altivar Process Drive.

Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)

Environment:
All serial numbers for Altivar Process Drive

Cause:
To configure the Comm. Scanner (Input/Output) tables:

Resolution:
Programming from the Drive:
  • [Communication] [Comm parameters] [Modbus SL] [Modbus Fieldbus] [Com. scanner input]
    • Up to 8 input registers can be configured
    • By default the first 2 registers are pre-configured
      • [Scan. IN1 address] nMA1 - 3201 (EtA Status word)
      • [Scan. IN2 address] nMA2 - 8604 (rFrd - Output frequency)
  • [Communication] [Comm parameters] [Modbus SL] [Modbus Fieldbus] [Com. scanner output]
    • Up to 8 output registers can be configured
    • By default the first 2 registers are pre-configured
      • [Scan.Out1 address] nCA1 - 8501(CMd word)
      • [Scan.Out2 address] nCA2 - 8602(LFrd - Output freq in rpm)



Programming from Somove:
  • [Parameter List] [Fieldbus] [Port - Modbus Serial] [Modbus Fieldbus]
screenshot

NOTE: This is not the same as the I/O scanning table that is used with Ethernet communications.


Schneider Electric Vietnam

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: