You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
Issue:
Scaling the Analog Output when using Output Power on an ATV61/71.
Product Line:
ATV61/ATV71
Environment:
All models, All serial numbers
Cause:
N/A
Resolution:
The output power (OPR) function is scaled between 0 and 2.5X the NPR (Rated motor power) setting under menu 1.1 (Simply Start). This parameter should be set to match the horsepower or KW rating of your motor in order for the output scaling to be accurate.
Scaling the Analog Output when using Output Power on an ATV61/71.
Product Line:
ATV61/ATV71
Environment:
All models, All serial numbers
Cause:
N/A
Resolution:
The output power (OPR) function is scaled between 0 and 2.5X the NPR (Rated motor power) setting under menu 1.1 (Simply Start). This parameter should be set to match the horsepower or KW rating of your motor in order for the output scaling to be accurate.