{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
What causes OFS to give a Polling rate overrun message?
Polling Rate Overrun is when OFS is requesting too much data and the PLC is not able to respond in a timely manner.  The Minimum Update Rate could be increased to give the PLC more time to respond.

-Locate the file named 'OFSinternal.xml' and make a backup copy of it. It should be in the following path: C:\ProgramData\Schneider Electric\OFS\3.60.0.0\
-Open the file named 'OFSinternal.xml' using 'Wordpad.
-Change the view to 'Word wrap to ruler'.
-Change the value of the "MinUpdateRate" value="1000".
-Save the changes.

NOTE:  The path above is for OFS v3.6 but it will also work for v3.5 but the path will be different.

Schneider Electric Vietnam

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: