Parameters to set up in a ATV320 Drive.
Product Line:
Altivar 320
Environment:
All ATV320 drives
Cause:​
Basic programming
Resolution:
CONF>FULL>SIM
tFr= Max frequency
ItH= Motor thermal Current (motor FLA)
ACC= ramp up time
dEC= ramp down time
LSP= Low speed
HSP= High speed
CONF>FULL>drC
bFr= Base motor frequency 60hz
CONF>FULL>drC>ASY
nPr= HP of the motor
UnS= Rated motor voltage
nCr= Rated motor current (Motor FLA)
FrS= Rated motor frequency
nSP= Rated motor speed (RPM)
CONF>FULL>SET
CLI= current limit (maximum current, must be greater than FLA, up to 150% of FLA)
NOTE: Make sure to use the information on your motor's nameplate for programming.
Please refer to ATV320 Programming Manual, document # NVE41295 for additional details.