{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.

How do I perform a Static Test Check on an Altivar Process Drive?

Article available in these languages: Spanish

Issue:
Performe a Static Test on an Altivar Process.

Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950)

Environment:
All serial numbers for Altivar Drives

Cause:
Test needed to check for short

Resolution:
Checking The Input and Output Diode Bridges
This test is done using a digital multi-meter in diode test mode to check that the transistors and diodes are not short-circuited.


ALL TESTS ARE TO BE PERFORMED WITH ALL SOURCES OF POWER REMOVED FROM THE DRIVE

For Altivar Process Drive up to 25hp
  • Range: ATV630...  ATV930....
    • U07M3 to D18M3 and U07N4 to D18N4
  • Range: ATV650... ATV950...
    • U07N4 to D18N4
  • Drive uses all diodes on the Input and Output Diode Bridge.
  • Instrument
    • Use Digit-Meter with a diode scale
  • Measurement
    • ​Locate PA+ and PC- input on drive power terminals (should be close to your power connection terminals)
    • Set meter to diode scale
    • To measure Input diodes
      • Place black on positive bus (PA+) and red on L1
      • Get readings and then move to L2, and then L3
      • When done swap red and black probes, and measure again between (PA+) to L1...L3
      • Repeat the entire procedure measuring from PC- instead of PA+.
      • Readings should be OL (should be above 1.0 and may continue to increase to OL if the meter is left connected long enough) in one direction and a low voltage reading the other way (Example 0.3v)
    • To measure Output diodes
      • Place black on positive bus (PA+) and red on T1
      • Get readings and then move to T,2  and then T3
      • When done swap red and black probes , and measure again between (PA+) to T1...T3
      • Repeat the entire procedure measuring from PC- instead of PA+
      • Readings should be OL in one direction and a low voltage reading the other way (Example 0.3v)
      • d
For Altivar Process Drive over 25hp
  • Range: ATV630...  ATV930....
    • D22M3 to D75M3 and D22N4 to C31N4
  • Range: ATV650... ATV950...
    • D22N4 to D90N4
  • Drive uses SCRs on the positive input bridge and diodes on the negative. For the Output Bridge its all diodes.
  • Instrument
    • Use Digit-Meter with an ohm and a diode scale
  • Measurement
    • ​Locate PA+ and PC- input on drive power terminals (should be close to your power connection terminals)
    • To measure Input SCRs and diodes.
      • Set meter to diode scale
      • Place black on positive bus (PA+) and red on L1
      • Get readings and then move to L2, and then L3
      • When done swap red and black probes and measure again between (PA+) to L1...L3
      • Readings should be 1.0 - OL in both directions (should be above 1.0 and may continue to increase to OL if the meter is left connected long enough).
      • Set meter to diode scale
      • Place black on positive bus (PC-) and red on L1
      • Get readings and then move to L2 ,and then L3
      • When done swap red and black probes and measure again between (PC-) to L1...L3
      • Readings should be OL in one direction and a low voltage reading the other way (Example 0.3v)
    • To measure Output diodes
      • Place black on positive bus (PA+) and red on T1
      • Get readings and then move to T2 ,and then T3
      • When done swap red and black probes and measure again between (PA+) to T1...T3
      • Readings should be OL in one direction and a low voltage reading the other way (Example 0.3v)

f

Schneider Electric Vietnam

Explore more
Range:
Altivar Process ATV600Altivar Process ATV900
Explore more
Range:
Altivar Process ATV600Altivar Process ATV900
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.