You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
Issue:
A1U1 parameter does not show up in the Fr1 menu on the ATV320 drive.
Product Line:
Altivar ATV320
Environment:
All
Cause:
Wants to setup the knob as the speed control
Resolution:
A1U1 will only show up in the Fr1 menu when you assign CHCF to SEP (Profile= Separate). Changing the value of this parameter requires holding the enter button for 2 seconds.
A1U1 parameter does not show up in the Fr1 menu on the ATV320 drive.
Product Line:
Altivar ATV320
Environment:
All
Cause:
Wants to setup the knob as the speed control
Resolution:
A1U1 will only show up in the Fr1 menu when you assign CHCF to SEP (Profile= Separate). Changing the value of this parameter requires holding the enter button for 2 seconds.