{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.

Connecting an EGX150 to a serial RS485

Article available in these languages: Spanish

Issue
The Serial port for the EGX150 uses an RJ45 connector, which is different from the standard RS-485 connector.

Product Line
Link150, EGX150

Environment
EGX150 serial connections

Cause
The EGX150 does not use the standard RS-485 connector.

Resolution
Pin NumberColourSignal nameDescription
1Orange/White stripedRx-Receive Data -
2OrangeRx+Receive Data +
3NCNo Connection
4BlueTx+Transmit Data +
5Blue/white stripedTx-Transmit Data -
6NCNo Connection
7NCNo connection
8GNDGround













Connect, using a straight through RJ45 cable to the RS-485 port on your EGX150.
Cut the other end (that is to be connected to your slave device) to expose the wires.

2-Wire RS-485 connection:
Use the Blue wire as the positive (+) and the Blue/White striped wire as the negative (-)
RS485 2-Wire Connection Diagram

4-Wire RS-485 connection:
RJ45 Pin Number MasterSlave
1Rx-Tx-
2Rx+Tx+
4Tx+Rx+
5Tx-Rx-







RS485 4-Wire Connection Diagram

Kindly refer to the EGX150 User Guide for details on how to wire the RS-485 port.

Schneider Electric Vietnam

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: