{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
Why won't the ATV320 drive output full voltage at 60hz?
Issue:
ATV320 output not at full voltage at 60hz

Product Line:
ATV320

Environment:
All serial numbers

Cause:
Drive ramps to speed (60z). The max drive output voltage is only 10 volts with "no" drive fault.

Resolution:
Set  MPC  to COS
DRI- > CONF > FULL > DRC- > ASY
MPC   [Motor param choice] >  [Mot Power]  = (nPr), change to COS   [Mot Cos] (COS)

Schneider Electric Vietnam

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: