You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
Unity Pro calculates automatically Power Budget for controller configuration, based on maximum Power consumption of modules configured. It generates a warning in case total Power budget is superior to the Power supplied.
The BME NOS 0300 Power consumption budget taken into account by Unity Pro versions V13 and below (V12, V11.1) is not correct.
Unity Pro V13 (and below) states:
3,3V 0,5A 1,8W
While the correct values are :
3.3V 0,02A 0.066W
24V 0,2A 4.8W
Those values will be updated in next Unity Pro release (V13.1)
The BME NOS 0300 Power consumption budget taken into account by Unity Pro versions V13 and below (V12, V11.1) is not correct.
Unity Pro V13 (and below) states:
3,3V 0,5A 1,8W
While the correct values are :
3.3V 0,02A 0.066W
24V 0,2A 4.8W
Those values will be updated in next Unity Pro release (V13.1)