How do you program a logic input for fault reset on the ATS48 soft starter?
Issue:
Program a logic input for fault reset on the ATS48 soft starter.

Product Line:
ATS48

Environment:
All

Cause:
Wants to set up a logic input to reset faults

Resolution:
RDY
Arrow down to I/O enter
Arrow down to LI3 enter
set LI3 set to LIr

Schneider Electric Vietnam