Video: Can I read a Float Value with a Read_Var SoMachine 4.3 ?
You will need to assign a variable to %MDx Location and Read at least 2 registers where the Float is located on your Remote Device. Move the Registers into %MWx*2 and %MWx*2+1.

See Attached project archive file for example. The following video demonstrates this procedure:

Schneider Electric Vietnam

Attachment(s)
M251_Read_Float_Ethernet_projectarchive.zip [2.3 MB]