{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
I need the waveform disturbance recording for Io without core balance CT connected, how can I do?
Use so called Holmgren or sum connection  instead of IoCalc mode and choose measured Io as channel.

Schneider Electric Vietnam

Attachment(s)
sum connection.JPG.jpg [16.39 KB]
Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: