What is the meaning of the Max switch-on time parameter valid for an external braking resistor connected to the Servo drive Lexium LXM32
Resext_on, the max permissible switch-on time for external braking resistor is max continuous period for current delivered to external braking resistor. After this time at the latest, there must be a "pause" inserted. During the pause, no current is delivered to the braking resistor. The purpose is to balance resistor temperature and to avoid a high rise of temperature followed by long fall (cooling during pause).
The parameter should not be greater than 10% of the resistor time constant.
On the other hand, the parameter should not be very small as it can limit the current delivery and braking dynamics for high inertia loads.

Schneider Electric Vietnam

You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
What is the meaning of the Max switch-on time parameter valid for an external braking resistor connected to the Servo drive Lexium LXM32
Resext_on, the max permissible switch-on time for external braking resistor is max continuous period for current delivered to external braking resistor. After this time at the latest, there must be a "pause" inserted. During the pause, no current is delivered to the braking resistor. The purpose is to balance resistor temperature and to avoid a high rise of temperature followed by long fall (cooling during pause).
The parameter should not be greater than 10% of the resistor time constant.
On the other hand, the parameter should not be very small as it can limit the current delivery and braking dynamics for high inertia loads.  

Schneider Electric Vietnam

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:

Need help?

  • Product Selector

    Quickly and easily find the right products and accessories for your applications.

  • Get a Quote

    Start your sales enquiry online and an expert will connect with you.

  • Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

  • Help Centre

    Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.