{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.

Why can't I see entries like FR1, CHCF, or CD1 in CoE in ATV320 VFDs with VW3A3601 EtherCAT comm card?

Issue:
Entries like FR1, CHCF, or CD1 in CoE in ATV320 VFDs with VW3A3601 EtherCAT comm card.

Product Line:
ATV320

Environment:
All

Cause:
Having access to these parameters through CoE allows easier configuration and also the potential for automated configuration.

Resolution:
Need V1.12 ESI file. It corrects the problem.

Schneider Electric Vietnam

Explore more
Range:
Altivar Machine ATV320
Explore more
Range:
Altivar Machine ATV320
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.