{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
What would cause the ATV600 or ATV900 to show Run 0.0hz if I'm not using anything external to adjust the speed?
Issue:
What would cause the ATV630 to show Run 0.0hz if I'm not using anything external to adjust the speed?

Product Line:
ATV630

Environment:
All


Cause:
Programming


Resolution:

If you're not using an external speed reference (i.e. Potentiometer, Transducer, etc.), when you close 24v to DI1 the drive shows 0.0hz.  You will need to go to [Simply Start] set [Low Speed] to 60hz (or desired speed)

Schneider Electric Vietnam

Explore more
Range:
Category:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
Category: