Does Vijeo Designer Runtime support the DNP3 protocol?
Issue:
Cannot find a DNP3 Protocol in Vijeo Designer. Is it supported by the Magelis HMIs?

Product Line:
Vijeo Designer (all versions)

Resolution:
The Vijeo Designer Runtime does not support the DNP3 Protocol. Considering using a M340 PLC to communicate over DNP3 and then have the Vijeo Designer Runtime communicate to the M340 PLC over Modbus TCP/IP.